Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
The controller is supplied with the proportion of windows set to 50 % so that the com-
posite outside temperature represents the mean value of actual and filtered outside
temperature.
It is calculated as follows:
Toeff = (0.5 × To) + (0.5 × Tofil)
0
5
10
15
20
25
ToStrDmp
Toeff
t
31
31D
23
To
To
Main menu > Settings > Heating circuit > Space heating
Operating line
Range
Factory setting
Building time constant.
0…200 h
20 h
Main menu > Heating circuit > Heating curve
Operating line
Range
Factory setting
Proportion of windows
0…100 %
50 %
10.6.2 Heating curve
)
The heating curve is defined by 2 curvepoints:
1
: At the design temperature
•
Outside temperature ToDe
A
•
Flow temperature SpTFlDe
B
2
: At the theoretical heating limit
•
Outside temperature ToHi
C
•
Flow temperature SpTFlHi
D
SpTFlDe
SpTFlHi
SpTRN
TFl
TOeff
TODe
sHC
TOHi
B
D
A
C
1
2
31
31
D
24
The nonlinear heat transmission is considered by the radiator exponent nH. The follow-
ing table gives an overview of the heating systems normally used:
p
Window
= 50%
Settings
Heating curve
Curvepoints
Radiator exponent