Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
In the event of a flow sensor error, the mixing valve will be driven to the fully closed
position to become inactive (in case of a 3-position actuator); it can then be operated
manually.
Number Text
Effect
51
[HC 1] error return
sensor
Nonurgent message; must be acknowledged
Behaves like a heating circuit without return temperature sensor. Return temperature
limitation is inactive.
Number Text
Effect
60
Room sensor error
plant 1
Nonurgent message; must not be acknowledged
61
>2 room sensors in
plant 1
Urgent message; must be acknowledged.
More than 2 room temperature sensors in the
same geographical zone.
Number Text
Effect
10
Outside temp sensor
error
Nonurgent message; must not be acknowledged
11
>1 outside tempera-
ture sensor
Urgent message; must be acknowledged.
More than 1 outside sensor in the same outside
temperature zone.
12
Outs sensor simula-
tion active
Nonurgent message; must not be acknowledged
Number Text
Effect
5401
Room master failure in
plant 1
Nonurgent message; must not be acknowl-
edged
No master
5402
>1 room master [1]
Nonurgent message; must not be acknowl-
edged.
More than 1 master
No. Text
Effect
2521
[Heat circuit pump]
overload
2522
[Heat circuit pump B]
overload
2523
[Heat circuit pump]
no flow
2524
[Heat circuit pump B]
no flow
2525
[Heating circuit
pump] fault
Sensor error, return tem-
perature
Sensor error, room tem-
perature
Sensor error, outside
temperature
Error room control combi-
nation
Fault heating circuit
pump