158/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
Priority Name
Explanation
e
External master
If the heating circuit operates in a room control
combination as a slave, the operating mode is
preselected by the external master (heating
circuit or ventilation).
In that case, interventions of priority
f
through
can only be made on the master
f
Room optg mode contact
Using the room operating mode contact, a fixed
operating mode can be preselected. This oper-
ating mode overrides the room operating mode
selector
g
on the controller
g
Room optg mode selector The room operating mode selector can be used
to switch from
mode to a continuous
operating mode with an appropriate setpoint.
In
mode, the setpoint is determined by
the time switch or the presence button and timer
function
h
i
/
j
Presence and timer button The current time program can be overridden by
presence button
h
or timer button
i
.
The timer button at digital input
j
(or of a third-
party Konnex device) can also override the
room operating mode.
If 2 or more functions are triggered, the function
activated last will prevail.
k
Special day contact
The current 24-hour program gets overridden by
the special day contact. The special day pro-
gram is activated in the time switch
l
Holiday contact
The current 7-day program will be overridden by
the holidays contact. The room operating mode
can be selected
Calendar
If a special day is active, the associated 24-hour
program of the time switch will be activated.
Holidays, if entered, will be overridden. If holiday
mode is active, the selected room operating
mode is used
Time switch
In the time switch, the associated 24-hour pro-
gram will be activated in accordance with the
current weekday. The 24-hour program passes
on the current room operating mode, the next
setpoint, and the time up to the next switching
point
10.6 Weather-compensated heating circuit
control
The flow temperature setpoint of heating circuit control is determined by the heating
curve and other influencing factors.
The main compensating variable of heating circuit control is the outside temperature. It
can be acquired by different sources:
•
By the locally connected outside sensor
•
Via bus from some other device
Outside temperature