61/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
5 General functions, fundamentals
01.03.2005
Entry Effect
Diagram
Master
The holidays/special days program in this
controller is active.
The holidays/special days program also acts
on all other controllers where the holi-
days/special days program is switched off
(slave) and which lie in the same holi-
days/special days
zone
.
31
4
0Z09
Main menu > Commissioning > Communication > Holidays/special days
Operating line
Range
Factory setting
Holidays/special day operation
Autonomous / Slave /
Master
Autonomous
Hol/spec day zone
1…31
1
For more detailed information about the setting regarding the communication of holi-
days/special days, refer to chapter 13 “Communication”.
5.2.2 Holidays
Holidays are periods of time
•
during which the building is not occupied
•
whose start and duration are known in advance
Examples:
•
Works holidays in commercially used spaces and buildings
•
School holidays in school buildings
•
Public holidays
It is possible to enter whether, during the holiday period, Economy or Protection mode
shall be used. For DHW heating, operating modes Auto
, Normal
, Reduced
and
Protection
are available.
Main menu > Holidays/special days
Operating line
Range
Factory setting
Room operating mode holidays
Economy,
Protection
Economy
DHW operating mode holidays
Auto
Normal
Reduced
Protection
Protection
If the controller is connected to other controllers via communication and if it is defined
as a master, the operating mode selected on it applies to all controllers in the same
holidays/special day zone.
If DHW heating lies in the same holidays/special day zone, the operating mode se-
lected under “DHW operating mode holidays” will apply during the holiday period.
5.2.3 Special
days
Special days are periods of time during which the building is used for special purposes
and whose start and duration are known in advance. These are especially public holi-
days.
The 7-day program can accommodate an additional 24-hour program (special day) as a
special day program. The setting is described in section
5.1 “Time switch”
.
If the controller (master) is connected to other controllers (slaves) via communication, a
specific 7-day program can be entered as a special day on each of the controllers
Setting