Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
7 Boiler temperature control
01.03.2005
Operating line
Range
Factory setting
Signal delay start
00.05…59.55 m.s
04.00 m.s
Signal interruption operation
00.00…59.55 m.s
20.00 m.s
Impact of fault
No stop / Stop
Stop
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Fault settings > Checkb sign shutoff valve
Operating line
Range
Factory setting
Signal delay start
00.05…59.55 m.s
02.00 m.s
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Fault settings > Flue temp supervision
Operating line
Range
Factory setting
Flue gas temperature limit value
---- / 8…400 °C
---- °C
Impact of fault
No stop / Stop
No stop
Fault priority
Urgent / Not urgent
Nonurgent
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Fault settings > Fault input 1
Operating line
Range
Factory setting
Fault text
A…Z
Water shortage
Impact of fault
No stop / Stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status signal delay
00.00…59.55 m.s
00.05 m.s
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Fault settings > Fault input 2
Operating line
Range
Factory setting
Fault text
A…Z
Overpressure
Impact of fault
No stop / Stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status signal delay
00.00…59.55 m.s
00.05 m.s
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Fault settings > Fault input 3
Operating line
Range
Factory setting
Fault text
A…Z
Underpressure
Impact of fault
No stop / Stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status signal delay
00.00…59.55 m.s
00.05 m.s
The type of fault input can be parameterized at menu item
Settings > Inputs
at the rele-
vant terminal.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs
Operating line
Range
Factory setting