48/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
01.03.2005
Main menu > Data backup
Operating line
Remarks
Restore
Important: Caution! New configuration
Save
Important: Caution! Stored data will be
overwritten.
3.9 Device
information
On the “Device information" menu, information about the controller, such as the soft-
ware version, can be viewed.
Main menu > Device informations > Controller
Operating line
Remarks
Plant type
Display of plant type
Plant type adapted
Display of an intervention made in the pro-
grammed application (yes, no)
File name
Has a function only in connection with
ACS7… Display of file name of the applica-
tion currently loaded
Can be edited under
Settings > Texts
.
Device type
RMK770-…
Software version
Display of software version
Hardware version
Display of hardware version
Main menu > Device informations > Position 1
or
2
or
3
Operating line
Remarks
Extension module
Display of the module’s type reference
Software version
Display of software version
Hardware version
Display of hardware version
3.10 Leaving the password level
On completion of commissioning, select the user level (access level for the plant opera-
tor). To do this, proceed as follows:
1. After completion of commissioning, you reach the main menu again.
2. Press the OK knob and the ESC button simultaneously.
3. The ”Access level” menu appears.
4. Select the user level by turning the OK knob.
5. Confirm selection by pressing the OK knob.
3.11 Marking
changes
If the internal standard application has been adapted or, if subsequently, submenu
"Extra configuration" has been accessed, an asterisk is placed in front of the plant
type’s type reference.
The asterisk denotes that the basic type was complemented by extra functions.
The asterisk is set automatically when leaving the "Extra configuration" menu, even if
nothing has been changed. In addition, on operating line ”Plant type adapted” of the
”Device information” menu, the value is set to ”Yes”.
The asterisk will be deleted and the line “Plant type adapted” shows the value as “No” if
on the “Basic configuration” menu, the old or a new standard application is loaded for
the plant type. A new configuration is made based on the selected application.
Setting
Display values
Marking
Resetting the marking