46/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
01.03.2005
3.5
Several boiler sequence controllers RMK770
If the number of outputs do not suffice although all extension modules are fully used, or
if the number of available function blocks do not suffice, the multiboiler plant must be
assigned to several RMK770. But there may also be other reasons to have the plant
controlled by several RMK770.
In that case, one of the RMK770 will assume the function of boiler master. And only in
that RMK770 is function block “Boiler sequence manager” activated. That function block
controls the boilers of the other RMK770 via bus.
The boiler master is defined by configuring the main flow temperature sensor.
With the other RMK770, that sensor must not be configured.
Configuration with the second RMK770 is made with setting “Basic type K“. In the extra
configuration, the sensors and aggregates must be assigned to the relevant boiler. In
the illustration below, this is boiler no. 3.
T
T
T
T
31
32
S
4
3
CE-
Q11
D1
X8
Q24
Q23
G0
M
M
Y1
G1
G
G1
X6
M
X5
M
M
M
X3
X2
M
X4
M
Q33
Q34
Q41
Q44
Q53
Q54
Q63
Q64
Q14
CE+
X1
G1
Q12
Q42
Q73
Q74
Y2
G0
X7
D2
M
M
G1
G0
G1
RMK770
T
RMZ78…
1
2
3
Common plant components (main pump, system pump, primary controller) must also
be connected to the controller with the boiler master.
If in total more than two boilers are in operation, the number of boilers must be set on
the boiler master.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler sequence manager
Operating line
Range
Factory setting
Number of boilers
1…6 2
Communication between the 2 RMK770 takes place via Konnex bus. It must be acti-
vated via the “Communication” menu. For more detailed information, refer to chapter 13
“Communication”.
3.6 Wiring
test
A
wiring test can be made with all connected peripheral devices. On completion of the
configuration and after having made all settings, it is recommended to conduct this test.
At the inputs, the current states or values are displayed.
Communication
Inputs