Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
10.7.2 Load
control
The heat output of mixing valve control can be reduced by functions of higher priority
(e.g. by return temperature limitation) or by functions of other plant (boiler, DHW heat-
ing). This is accomplished via load control.
T
T
31
31
B
1
5
T
Heat
consumer
Heat
source
Load control
Heat demand
Heat
consumer
Load reduction can be triggered by one of the following functions:
•
Protective boiler startup
•
Limitation of the return temperature
•
DHW heating with shifting priority
•
DHW heating with absolute priority
A load increase can be in the form of pump and / or mixing valve overrun. In principle,
this merely means load maintenance.
10.8 Optimization
functions
The optimization functions are activated or influenced by the following settings:
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Optimizations/influences
Operating line
Range
Factory setting
Type of optimization
With room model / With
room temp sensor
With room model
Forward shift on max
0…48 h
0 h
Early shutdown max
00.00…06.00 h.min
00:00 h.min
Quick setback
Off / On
On
[Boost heating] setpoint increase
0…20 K
5 K
Room temperature rise
1…600 min/K
60 min/K
10.8.1 Type of optimization
The type of optimization decides whether the optimization functions and boost heating
shall be performed based on the measured room temperature or whether the room
model shall be used.
In plant where the heating circuit operates in connection with a ventilation system as a
room control combination, the room temperature sensor of the ventilation plant must
not
be located in the extract air!
Load reduction
Load increase
Settings
Caution