144/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
9 Precontrol
01.03.2005
Number Text
Effect
2201
Heat requisition mod error Nonurgent message; must not be acknowl-
edged
An error at the input will be interpreted as “No heat demand”.
No. Text
Effect
2501
[System pump] overload
2502
[System pump B] overload
2503
[System pump] no flow
2504
[System pump B] no flow
2505
[System pump B] fault
Urgent, must be acknowledged and reset
9.10 Diagnostic
choices
Main menu > Primary controller > Inputs/setpoints
Operating line
Range
Actual value flow temp
…°C
Flow temperature setpoint
…°C
Actual value return temp
…°C
Return temperature max
…°C
Return temperature min
…°C
Heat requisition modulating
---- ( = not connected) / …°C
Heat requisition 2-position
0 / 1 (1 = closed)
DHW requisition 2-pos
0 / 1 (1 = closed)
Frost prot requisition 2-pos
0 / 1 (1 = closed)
[System pump] overload
0 / 1 (1 = overload)
[System pump B] overload
0 / 1 (1 = overload)
Flow signal pump
Main menu > Primary controller > Outputs
Operating line
Range
System pump
Off / On
System pump B
Off / On
Mixing valve 3-pos
Closing / ---- / Opening
Mixing valve modulating
0…100 %
Main menu > Primary controller > Limitations
Operating line
Range
Flow temperature max
Inactive/ Active
Flow temperature min
Inactive/ Active
Flow temperature rise
Inactive/ Active
Return temperature max
Inactive/ Active
Return temperature min
Inactive/ Active
Error heat requisition
modulating
Fault primary control-
ler or
system pump