Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
01.03.2005
System pump B, if the system pump is a twin pump.
3-position or modulating mixing valve for precontrol.
For more detailed information, refer to chapter 9 “Precontrol”.
3.4.4 Hydraulics-dependent
inputs and outputs of function
block “Heating circuit“
T
T
TRtCo
TRtMn
T
TMnFl
T
T
T
PrCtrVlvMx
TRtPrCtr
TFlPrCtr TPu_A
T
T
T
TRtHCtr
TFlHCtr HCtrPu_A
T
T
T
TFlHCtr
HCtrVlvMx
TRtHCtr
HCtrVlvMx
HCtrPu_A
T
Tr
TPu_B
HCtrPu_B
HCtrPu_B
T
Tr
31
32
S
5
5
Main menu > Commissioning > Extra configuration > Heating circuit
Operating line
Range
Factory setting
Heating circuit
Active / Inactive
Inactive
Main menu > Commissioning > Extra configuration > Heating circuit
Operating line
Range
Factory setting
Heat req heat circuit acting on
Main distributor / Primary
controller
Main distributor
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs
Operating line
Range
Name
Flow sensor
RMK770…, RMZ7…*
TFlHCtr
Room sensor
Tr
Return sensor
TRtHCtr
* Here, the free inputs are available for selection
Main menu > Commissioning > Extra configuration > Primary controller > Outputs
Operating line
Range
Name
Heating circuit pump
RMK770…, RMZ7…*
HCtrPu
Heating circuit pump B
HCtrPu_B
Mixing valve 3-pos
HCtrVlvMx
Mixing valve modulating
HCtrVlvMx
* Here, the free inputs are available for selection
Function block “Heating circuit” can be used as a “virtual heating circuit“. It calculates a
weather-compensated flow temperature setpoint, but does not deliver any output sig-
nals (hence, pump or mixing valve for the heating circuit is not a mandatory require-
ment!). The weather-compensated flow temperature setpoint is delivered to the main
flow and acts as weather-compensated heat demand.
System pump B (TPu_B)
Mixing valve
(PrCtrVlVMx)
Virtual heating circuit