96/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
6 Boiler sequence management
01.03.2005
Operating line
Range
[Boil address no 3] actual temp
[Boil address no 4] actual temp
[Boil address no 5] actual temp
[Boil address no 6] actual temp
or
Main menu > Boiler sequence manager > Inputs / Setpoints
Operating line
Range
Main flow temp actual value
Main flow temp setpoint
Main return temp actual value
MBRT. Return temp actual value
MBRT. Return temp minimum
Consumer return actual value
Release input
Heat requis modulating
Heat requisition 2-position
DHW requisition 2-pos
Frost prot requisition 2-pos
or
Main menu > Boiler sequence manager > Fault inputs
Operating line
Range
Fault text
Fault text for fault input 1
Fault input 1
Fault text
Fault text for fault input 1
Fault input 2
Fault text
Fault text for fault input 1
Fault input 3
[Main pump] overload
[Main pump B] overload
Flow signal pump
or
Main menu > Boiler sequence manager > Outputs
Operating line
Range
Main pump
Main pump B
Maint boiler return temp 3-pos
Maint boiler return temp mod
or
Main menu > Boiler sequence manager > Limitations
Operating line
Range
MBRT. Return temp minimum
Setpoint maximum limitation
6.8 Error
handling
Number Text
Effect
330
Main flow sensor error
Urgent message; must be acknowledged
and reset, plant stop
331
Main return sensor error
Nonurgent message; must be acknowl-
edged, no plant stop
Error main flow and
main return temperature
sensor