Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
6 Boiler sequence management
01.03.2005
6.2 Configuration
By selecting a plant type in the basic configuration, function block “Boiler sequence
manager“ will be activated. If several RMK770 are used, the function of boiler sequence
manager is always assumed by the RMK770 that can acquire a measured value of the
main flow temperature.
A plant type always requires the configuration of a main flow temperature sensor and a
main return temperature sensor. If more than 1 RMK770 is used for a boiler sequence,
these sensors may only be configured with the active “Boiler sequence manager” func-
tion block.
For each boiler sequence, use of a main flow temperature sensor is highly recom-
mended.
If there is no main flow temperature sensor, the following configuration adopts the meas-
ured value inside the controller from the boiler sensor of the current lead boiler:
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs > Main
flow sensor: autonomous
This variant can only be used with dual-boiler plant.
The main return temperature sensor is highly recommended in connection with a pres-
sureless header; but its configuration can also be deleted.
In the extra configuration, the basic configuration can be complemented and / or
amended.
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs
Operating line
Adjustable values / remarks
Main flow sensor
Terminal marking / autonomous
Main return sensor
MBRT return sensor
Sensor for maintained main boiler return
temperature
Consumer return sensor
Return sensor on the consumer side
Boil sequence selection input 1
Control input 1 for boiler sequence selection
Boil sequence selection input 2
Control input 1 for boiler sequence selection
Boil sequence selection input 3
Control input 1 for boiler sequence selection
Release input
Release input for the boiler sequence
Fault input 1
Digital input for fault supervision of the boiler
sequence
Fault input 2
Digital input for fault supervision
Fault input 3
Digital input for fault supervision
[Main pump] overload
Digital input for fault supervision of the main
pump
[Main pump B] overload
Digital input for fault supervision of the main
pump B (in case of a twin pump)
Flow signal
Digital input for flow supervision of the main
pump
Heat requis modulating
Heat requisition 2-position
DHW requisition 2-pos
DHW requisition 2-position
Frost prot requisition 2-pos
Basic configuration
Extra configuration
Inputs