Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
12 Function block faults
01.03.2005
Following can be set for each fault status message:
Main menu > Commissioning > Settings > Faults > Fault input…
Operating line
Range
Factory setting
Fault text
Free text, max. 20 char-
acters
Aux 1
Fault status signal delay
00.00…59.55 m.s
00.05 m.s
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
None
Fault priority
Urgent / Not urgent
Not urgent
Impact of fault
No stop / Stop
Stop
Limit value fault on
0 / 1*
1
Limit value fault off
0 / 1*
0
* Depends on “Input identifier”
These settings can only be made if the relevant input has previously been activated in
the extra configuration.
For more detailed information, refer to section 12.4 “Fault properties”.
The text for the universal status inputs is predefined with Aux 1 through Aux 4. The
texts can be adapted.
Signal at the fault
input
Fault status mes-
sage
3131
D
31
Signal delay
The fault status signal delay is used to set the period of time a fault
must be pending to be handled as such.
Parameter setting “Stop“ at the universal fault inputs means that the entire boiler se-
quence will be shut down.
Number Text
Effect
9001
Aux 1
Effect in accordance with the settings
9002
Aux 2
Effect in accordance with the settings
9003
Aux 3
Effect in accordance with the settings
9004
Aux 4
Effect in accordance with the settings
The digital status inputs cannot be monitored. We recommend to use wiring ensuring
that the signal drops out when a fault is pending.
12.7.2 Analog fault input with limit value supervision
An analog input can be monitored for limit value crossings.
An input that is already configured can also be monitored. For example, the main flow
temperature sensor can be monitored to ensure that a maximum flow temperature will
not be exceeded.
Fault text
Fault status
signal delay
Effect of fault
Fault status messages
Error handling