Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
7 Boiler temperature control
01.03.2005
7.2.1 Burner
types
By selecting the plant type, the type of burner is predefined for 2 boilers of the boiler
sequence.
•
Kx.1: 1-stage burner
•
Kx.2: 2-stage burner
•
Kx.3: Modulating 3-position
The relevant outputs are preconfigured.
The outputs can be changed in the extra configuration.
First burner stage or basic stage of a modulating burner.
Second burner stage
Configuration of a pair of terminals for a modulating 3-position burner.
Available for selection are the remaining free terminal pairs (Q1/Q2, Q3/Q4, Q5/Q6) for
the open and the close signal. Normally, special terminal pairs are required (RC unit for
radio interference suppression; for more detailed information, refer to subsection 3.3.2
“Terminal assignment and properties of outputs”).
DC 0…10 V output for a modulating burner.
DC 0…10 V output as a boiler temperature setpoint for an external boiler temperature
controller.
If no control of the burner is required, the DC 0…10 V output can also be used for set-
point compensation of a boiler. In that case, it is not the boiler temperature that is con-
trolled, but the boiler temperature setpoint is shifted as a function of the main flow tem-
perature.
7.2.2 Boiler
hydraulics
The following pumps are usually present:
•
One boiler pump per boiler
•
The main pump for all boilers
It is also possible to use a boiler pump as a mixing pump or a combination of mixing
pump and main pump.
A
B
T
31
3
2S
6
2
T
31
3
2
S
6
3
T
313
2S
64
T
T
31
3
2S
6
5
T
Boiler pump
Boiler mixing
pump
Main pump
Boiler mixing pump and
main pump
•
Plant types K1.x and K2.x use 1 main pump
•
Plant type K3.x uses 1 main pump and 1 mixing pump
•
Plant types K4.x, K5.x and K6.x use 1 boiler pump
By assigning an output to boiler pump A, a boiler pump is activated for the boiler. In
terms of configuration, no difference is made between boiler pump and mixing pump.
Optionally, a twin pump can be used in place of the boiler pump. In that case, in addi-
tion to boiler pump A, boiler pump B in the extra configuration must be assigned an
output.
Burner stage 1
Burner stage 2
Modulating 3-position
Modulating burner mod
Setpoint compensation
Definition of pumps