Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
value, the lowering of the flow temperature setpoint will be gradually reduced. The
function operates with I-control action and an adjustable integral action time Tn.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Controller
Operating line
Range
Factory setting
[Tn] return temp limitation max
0…60 min
30 min
Minimum limitation of the return temperature uses a fixed integral action time.
10.4.3 Room temperature setpoint adjuster, absolute
For the preselected room temperature setpoints, Comfort and Precomfort, a remote
setpoint adjuster (e.g. BSG21.1) can be configured.
The 4 setpoints will be readjusted according to the following diagram.
21 °C
23 °C
25 °C
28 °C
19 °C
16 °C
z.B.:
SpCHCmf
+10 K
-10 K
0 K
0 K
0 K
32 °C
12 °C
SpHEco
SpCPreC
SpCCmf
SpHCmf
SpHPreC
SpCEco
SpCPrt
SpHPrt
0.5 K
3
1
31D
2
7
C
Cooling PreC Precomfort
Cmf Comfort
Prt Protection
Eco Economy
SP Setpoint
H Heating
The input is activated via the extra configuration:
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs >
Room setpoint adjuster abs
Assign terminal
There are no settings required.
It is not recommended to use a QAA25 room temperature setpoint adjuster since its
characteristic is not linear so that setpoint deviations of maximum 1 K would occur.
Compensation is not possible.
The adjusted setpoint represents the Comfort setpoint. At the same time, the Precomfort
setpoint is displaced parallel, which means that the difference between the 2 setpoints will
be maintained.
Minimal limitation
Extra configuration
Settings