10 Heating circuit control
01.03.2005
The ventilation controller’s room temperature sensor must not be installed in the extract
air duct! Otherwise, functions “Room temperature influence” and “Type of optimization”
with room temperature may not be activated.
10.5 Room operating modes and room tempera-
ture setpoints
10.5.1 Room operating modes
The room operating mode determines the preselected setpoint for the room tempera-
ture. The flow temperature setpoint, the heating limit and the optimization functions will
be influenced depending on the current room temperature setpoint.
Main menu > Heating circuit > Room operating mode
Operating line
Range
Factory setting
Preselection
Auto
Comfort
Precomfort
Economy
Protection
Auto
State
Comfort… Protection
Cause Time
switch
Holidays
l
or
Special day
k
or
Timer function
i
or
j
Room unit presence but-
ton
h
Room operating mode
selector
g
Room operating mode
contact
f
External master
e
The control priorities
e
… are explained in subsection 10.5.5 “Control priorities in the
heating circuit”.
Here, the plant operator can select the required operating mode. In operating mode
, the setpoint is determined by the time switch or the plant operator. If required,
it can be switched to continuous operation with a fixed setpoint.
In Protection mode, safety-related functions, such as frost protection, remain active.
The display shows the heating circuit’s setpoint that is currently maintained.
There may be various reasons for the current state. Decisive is the control priority (refer
to subsection 10.5.5 “Control priorities in the heating circuit”).
In
mode, the time switch switches the room operating mode or the setpoint
according to the program entered. During the holiday period, the setpoint is predefined.
Main menu > Holidays / Holidays/special days
Operating line
Range
Factory setting
Room operating mode holidays
Economy / Protection
Economy
The holiday function is only active in
mode.
Important
Room operating mode
Preselection
Room operating mode se-
lector
⇒
State
Cause
Time switch
Holiday operating
mode
Note