A
Troubleshooting
A-49
12.552 : EtherNet/IP overtime error
Code
: &H000C &H0228
Meaning/Cause
a. Communication error occurred by noise, etc. in the EtherNet/IP system.
b. The master module power is turned off or has stopped operating.
c. The cable is broken or unconnected.
Action
a. Take the noise preventive actions for the cable of the EtherNet/IP system and the controller.
b. Check that the master module operates correctly.
c. Check the EtherNet/IP cable connection.
12.561 : PROFIBUS link error
Code
: &H000C &H0231
Meaning/Cause
a. Error occurred in cable for PROFIBUS system.
b. The communication setting of the PROFIBUS system was incorrect.
c. The master module power is turned off, has stopped operating or is damaged.
d. The PROFIBUS compatible module is damaged.
Action
a. Check for a break disconnection, wiring error, short circuit on the PROFIBUS cable or the
specifications (cable length, etc.).
b. Check the communication setting.
c. Check that the master module operates correctly.
d. Replace the PROFIBUS compatible module.
12.562 : PROFIBUS overtime error
Code
: &H000C &H0232
Meaning/Cause
a. Communication error occurred by noise, etc. in the PROFIBUS system.
b. Master module power is turned off or has stopped operating.
c. The cable is broken or unconnected.
Action
a. Take the noise preventive actions for the cable of the PROFIBUS system and the controller.
b. Check that the master module operates correctly.
c. Check the PROFIBUS cable connection.
12.571 : PROFINET link error
Code
: &H000C &H023B
Meaning/Cause
a. Error occurred in cable for PROFINET system.
b. The communication setting of the PROFINET system incorrect.
c. The master module power is turned off, or the PLC has stopped operating, or is broken.
d. The PROFINET compatible module is breakdown.
Action
a. Check for a break disconnection, wiring error, short circuit on the PROFINET cable or the
specifications (cable length, etc.).
b. Check the communication setting.
c. Check that the master module operates correctly.
d. Replace the PROFINET compatible module.
12.572 : PROFINET overtime error
Code
: &H000C &H0232
Meaning/Cause
a. Communication error occurred by noise, etc. in the PROFINET system.
b. Master module power is turned off or has stopped operating.
c. The cable is broken or unconnected.
Action
a. Take the noise preventive actions for the cable and controller of the PROFINET system.
b. Check that the master module operates correctly.
c. Check the PROFINET cable connection.
12.581 : Counter1 wire breakage
Code
: &H000C &H0245
Meaning/Cause
The encoder cable connected to the counter 1 is broken. The break detection is available when
the counter 1 is set to "VALID".
Action
• Set the counter status to "INVALID" if the encoder is not connected to the counter 1.
• Check the encoder cable of the counter 1.
• Check if the encoder works normally.
Содержание YRCX Series
Страница 1: ...7 6HULHV DW 1R 1 5 5RERW RQWUROOHU 23 5 7 21 0 18 6 5 5RERWV 5 6HULHV...
Страница 2: ......
Страница 10: ......
Страница 12: ......
Страница 14: ......
Страница 20: ......
Страница 28: ......
Страница 164: ......
Страница 166: ......
Страница 178: ......
Страница 186: ......
Страница 264: ......
Страница 265: ......
Страница 266: ...DW 1R 1 XWKRUL HG LVWULEXWRU 3ULQWHG LQ XURSH...