11 Buffer Memory (Parameters & Monitored Data)
11.4 Control Data
246
FX
3U
-20SSC-H Positioning Block User's Manual
11.4.19 Manual pulse generator input selection [BFM #529]
Sets the MPG input selection (Ver.1.10 or later)
→
For details on the manual pulse generator, refer to Section 8.3
11.4.20 Ring operation rotation direction for absolute address
Sets the rotation direction when absolute address is specified in the ring operation. (Ver.1.10 or later)
→
For details on the ring counter setting, refer to Section 7.8
BFM Number
Description
Default
X-axis
Y-axis
BFM
#529
-
0: X input - X opr / Y input -Y opr
1: X input / Y opr
2: X input - X and Y opr
K0
BFM Number
Description
Default
X-axis
Y-axis
BFM
#530
BFM
#630
0: Direction for shorter rotation
1: Direction where the current value increases (clockwise)
2: Direction where the current value decreases (counterclockwise)
K0