7 Before Starting Positioning Operation
99
FX
3U
-20SSC-H Positioning Block User's Manual
1
Int
roduct
ion
2
Sy
stem
conf
igur
ati
on
3
Exam
ple
C
onnect
ion
4
Ins
tall
a
tion
5
Wi
rin
g
6
Me
m
o
ry
confi
gur
at
ion
and da
ta
7
Befor
e
star
ting
positi
oning
contr
o
l
8
M
anual c
ont
ro
l
9
Posit
ioni
ng
C
ont
rol
10
Table O
per
at
ion
7.6 Changing During Operation (Operation Speed, Target Address)
Change procedure
1) Set the following bits to OFF in operation command 1.
- Change command in operation disabled
- Target position change command in positioning operation
2) Set the target position change value (address) and target position change value (speed).
3) Set the target position change command in positioning operation to ON in operation command 1.
4) Set the following bits in operation command 1 as follows when the During operation speed change flag in
the status information turns OFF from ON.
- Set the target position change command in positioning operation to OFF.
- Set the change command in operation disabled to ON.
When unintended speed changes during operation are disabled except changes by change commands
(excluding speed changes using the override function)
Operation when the operation direction changes
When the operation direction changes due to a change of the target address, the system will decelerate and
stop, turn around, and then reach the newly set address.
Operation speed present value
BFM #11,#10
BFM #111,#110
Monitor data
Change command in
operation disabled
Operation command 1
BFM #518 b12
BFM #618 b12
Control data
Target position change
command in positioning
operation
Operation command 1
BFM #518 b14
BFM #618 b14
Control data
Target address
Target address 1
BFM #501,#500
BFM #601,#600
Control data
Target address 2
BFM #505,#504
BFM #605,#604
Control data
Target position change value (address)
BFM #515,#514
BFM #615,#614
Control data
Target position change value (speed)
BFM #517,#516
BFM #617,#616
Control data
Received target address (Ver.1.20 or later)
BFM #25,#24
BFM #125,#124
Monitor data
Received target speed (Ver.1.20 or later)
BFM #27,#26
BFM #127,#126
Monitor data
During target address
change
Status information
BFM #28 b14
BFM #128 b14
Monitor data
BFM Number
Data type
X-axis
Y-axis
ON
ON
OFF
OFF
Speed
Target address
New target
address
Time
Turnover
Target position change command
(speed) in positioning operation
Changing target address