7 Before Starting Positioning Operation
54
FX
3U
-20SSC-H Positioning Block User's Manual
7.1 Note on Setting Parameters
From the previous page
From the previous page
To the next page
To the next page
Parameter
setting
program
execution
flag
System
reset
execution
flag
Starts the system
reset program.
Set the parameter
setting program
completion flag.
Resets the parameter
setting program
execution flag.
Resets the system
reset execution flag.
Jump to an END
instruction.
M306
P1
Executes system reset. [Ver. 1.10 or later]
The power of the 20SSC-H is turned OFF once and then turned ON again
when the version is earlier than Ver. 1.10.
When turning ON power again, this ladder block is unnecessary.
The reboot of 20SSC-H needs 10ms or more after system reset.
When re-turning ON power, this ladder block is unnecessary.
Create the positioning operation program.
A positioning operation program and a parameter setting program should provide an interlock
in the program not to execute simultaneously.
In this program example, while the parameter setting program is executing, M300 is ON.
When turning ON power again, change the contact of T0 to M306.
And change "RST M308" to "RST M306."
1) Check that M500 is ON by using device monitor.
[Power OFF procedure]
2) Turn OFF the power.
3) Turn ON the power of the servo amplifier.
4) Turn ON the power of the PLC (including the 20SSC-H).
FNC 01
CALL
M300
M308
T0
T0
K1
Parameter
setting
program
completion
flag
Parameter
setting program
execution flag
M500
M300
RST
M300
RST
M308
SET
M500
P63
FNC 00
CJ