13 Diagnostics
13.2 Check Error Code
271
FX
3U
-20SSC-H Positioning Block User's Manual
11
Buffer
M
e
m
o
ry
12
Pr
ogr
am
Exam
ple
13
D
iagnostics
A
List
of
Par
a
m
e
ter
s and
Da
ta
B
V
e
rs
ion
Infor
m
at
ion
13.2.3
Error code list [BFM #29 (X-axis), BFM #129 (Y-axis)]
When an error occurs
,
an error code is stored in decimal to BFM #29 (X-axis) and BFM #129 (Y-axis).
Error category
Error
Code
(decimal)
Error Content
Action
-
0
No error
-
Setting error
2
Incorrect value range
A value outside of the setting range is set to the
buffer memory.
Change the setting value in buffer memory so that it
is within the setting range.
3
Value overflow
The converted pulse data (e.g. travel distance or
operation speed) exceeds 32 bits.
Change the setting value of the corresponding buffer
memory so that the converted pulse data is smaller
than 32-bit data.
5
The operation pattern has Multiple operation
patterns
Change the program in the PLC main unit so that
only one operation pattern is selected.
6
Center coordinate setting error
When one of the following applies:
-
Start point = center coordinate
-
End point = center coordinate
-
Center coordinate is outside of the
-2,147,483,648 to 2,147,483,647 PLS range
Check the center coordinate setting
and set so that a
circle is formed.
Control errors
3000
Table operation start No. error
The table No. is executed outside of the range 0 to
299.
Change the table operation start No. to 0 to 299.
3001
Jump No. fault
The jump No. for the table information
is set outside
the range 0 to 299.
Change the jump No. for the table information to 0 to
299.
3002
Command format fault
The operation information of the table information
is
set by a non-defined number.
Change the operation information of the table
information.
3004
Current value overflow at absolute value detection
system
The converted pulse data of the current address
exceeds 32 bits.
Turn the power OFF, or perform a mechanical zero
return or data set type zero return.
3005
Manual pulse generator input error
Change the pulse generator input (numerator)
and
pulse generator input (denominator) settings.
3006
Interpolation error during ring operation
Linear interpolation, linear interpolation (interrupt
stop) or circular interpolation is performed while the
ring operation is set.
Reset the ring operation setting before executing the
interpolation.