9 Positioning Control
9.5 Interrupt 2-speed Constant Quantity Feed
165
FX
3U
-20SSC-H Positioning Block User's Manual
1
Int
roduct
ion
2
Sy
stem
conf
igur
ati
on
3
Exam
ple
C
onnect
ion
4
Ins
tall
a
tion
5
Wi
rin
g
6
Me
m
o
ry
confi
gur
at
ion
and da
ta
7
Befor
e
star
ting
positi
oning
contr
o
l
8
M
anual c
ont
ro
l
9
Posit
ioni
ng
C
ont
rol
10
Table O
per
at
ion
Note
• Interrupt input is detected in the order of INT0 and INT1.
• The travel distance for target address 1 must be larger than the deceleration distance to stop.
If the travel distance for target address 1 is smaller, the work piece decelerates as much as possible, and
the operation stops.
→
For details, refer to Subsection 7.11.2
2. Operation speed
The actual operation speed is decided by the following calculation formulas.
- Operation speed 1
×
Override setting
- Operation speed 2
×
Override setting
The actual operation speed 1 and operation speed 2 can be changed using the operation speed change
function except under the following conditions.
→
For change of the operation speed, refer to Section 7.6
• During deceleration operation from operation speed 2
• When the speed change disable during operation signal is ON.
3. Address specification
Specified addresses are handled as relative addresses (travel distance from the current address).
(The absolute/relative address specification is ignored.)
4. Rotation Direction
The sign of the target address decides the operation direction.
+: Operates in the direction that increases the current value. (When the value is 0, it is regarded as 1.)
-:
Operates in the direction that decreases the current value.