APPENDIX
App. - 24
App. 5.7.2 Specifications
Safety logic unit model
MR-J3-D05
Voltage
24 V DC
Control circuit
power supply
Permissible
voltage fluctuation
24 V DC ± 10%
Power supply
capacity
[A]
0.5 (Note 1, 2)
Compatible system
2 systems (A-axis, B-axis independent)
Shut-off input
4 points (2 point × 2 systems)
SDI_: (source/sink compatible) (Note 3)
Shut-off release input
2 points (1 point × 2 systems) SRES_: (source/sink compatible) (Note 3)
Feedback input
2 points (1 point × 2 systems) TOF_: (source compatible) (Note 3)
Input type
Photocoupler insulation, 24 V DC (external supply), internal limited resistance 5.4 k
Ω
Shut-off output
8 points (4 point × 2 systems)
STO_: (source compatible) (Note 3)
SDO_: (source/sink compatible) (Note 3)
Output type
Photocoupler insulation, open-collector type
Permissible current: 40 mA/1 output, Inrush current: 100 mA/1 output
Delay time
setting
A-axis: Select from 0 s, 1.4 s, 2.8 s, 5.6 s, 9.8 s, or 30.8 s.
B-axis: Select from 0 s, 1.4 s, 2.8 s, 9.8 s, or 30.8 s.
Accuracy: ±2%
Functional safety
STO, SS1 (IEC/EN 61800-5-2)
EMG STOP, EMG OFF IEC/EN 60204-1)
Safety
performance
Standards certified
by CB
EN ISO 13849-1 Category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2, and EN 61800-5-2 SIL
2
Response
performance
(when delay time
is set to 0 s)
(Note 4)
10 ms or less (STO input off
→
shut-off output off)
Mean time to
dangerous failure
(MTTFd)
516 years
Diagnosis
converge (DC avg)
93.1%
Average
probability of
dangerous failures
per hour (PFH)
4.75 × 10
-9
[1/h]
Compliance
with standards
CE marking
LVD: EN 61800-5-1
EMC: EN 61800-3
MD: EN ISO 13849-1, EN 61800-5-2, EN 62061
Structure
Natural-cooling, open (IP rating: IP 00)
Environment
Ambient
temperature
0 °C to 55 °C (non-freezing), storage: -20 °C to 65 °C (non-freezing)
Ambient humidity
5 %RH to 90 %RH (non-condensing), storage: 5 %RH to 90 %RH (non-condensing)
Ambience
Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
Altitude
Max. 1000 m above sea level
Vibration
resistance
5.9 m/s
2
at 10 Hz to 55 Hz (directions of X, Y, and Z axes)
Mass [kg] 0.2
(including CN9 and CN10 connectors)
Note 1. Inrush current of approximately 1.5 A flows instantaneously when turning the control circuit power supply on. Select an
appropriate capacity of power supply considering the inrush current.
2. Power-on duration of the safety logic unit is 100,000 times.
3.
_: in signal name indicates a number or axis name.
4. For the test pulse input, contact your local sales office.
Содержание MR-J4-100A(-RJ)
Страница 19: ...10 MEMO ...
Страница 75: ...1 FUNCTIONS AND CONFIGURATION 1 56 MEMO ...
Страница 83: ...2 INSTALLATION 2 8 MEMO ...
Страница 159: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Страница 203: ...4 STARTUP 4 44 MEMO ...
Страница 351: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 40 MEMO ...
Страница 365: ...8 TROUBLESHOOTING 8 14 MEMO ...
Страница 387: ...9 DIMENSIONS 9 22 MEMO ...
Страница 403: ...10 CHARACTERISTICS 10 16 MEMO ...
Страница 553: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Страница 567: ...13 USING STO FUNCTION 13 14 MEMO ...
Страница 607: ...14 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 14 40 MEMO ...
Страница 639: ...15 USING A LINEAR SERVO MOTOR 15 32 MEMO ...
Страница 767: ...18 MR J4 03A6 RJ SERVO AMPLIFIER 18 84 MEMO ...
Страница 856: ...APPENDIX App 41 ...
Страница 905: ...MEMO ...