Chapter 4 Positioning Parameter & Operation Data
4-35
Remark
1. If you want to apply the input filter of the external input signal, signal of 2 control period or less is noe be
recognized On, because filter time is applied about 2 control period. In case that signals below 2 control
cycle is entered, it may become detected to On if the double High state is maintained.
2. Control period depending on the number of axes are as follows.
1ms: 1~2axes
2ms: 3~5axes
3ms: 6~8axes
3.
In modules that recognize the range for external input signal as ON/OFF
are as follows.
The input filter
‘0: Disable’
The input filter
‘1: Enable’
Period
Not recognized
Recognizable
Not recognized
Recognizable
1ms
-
Pulse width
> 1.05ms
Pulse width
< 1.9ms
Pulse width
> 2.1ms
2ms
-
Pulse width
> 2.1ms
Pulse width
< 3.8ms
Pulse width
> 4.2ms
3ms
-
Pulse width
> 3.15ms
Pulse width
< 5.7ms
Pulse width
> 6.3ms