Chapter 9 Functions
9-163
9.5.11 Infinite Running Repeat Function
Infinite Running Repeat Function means the function refreshing the command position and current position value
automatically and periodically with the value specified “Infinite Running Repeat Position” at extended parameter.
If you use this function, positioning with repeated position value for the same direction is available.
(1) Characteristics of Control
(a)
If you set “Infinite Running Repeat” of the Extended parameter as “1: Enable”, you can use “Infinite Running
Repeat” function.
(b) Set the position value to be
refreshed automatically at “Infinite Running Repeat position” of the extended
parameter.
(c) When “Infinite Running Repeat” parameter is “1: Enable”, command position and current position value are
expressed as 0 ~ “Infinite Running Repeat - 1”
(d) When setting “Infinite Running Repeat” parameter as “1: Enable”, if current position is out of the range of
Infinite Running Repeat, it will be changed into the value within the range of Infinite Running Repeat
automatically.
[Ex1] In case current position is 32100, infinite running repeat position is 10000,
When setting “Infinite Running Repeat” parameter as “1: Enable”, current position will be
2100.
[Ex2] In case current position is -32100, infinite running repeat position is 10000,
When setting “Infinite Running Repeat” parameter as “1: Enable”, current position will be
7900.
. (e) Setting the extended parameter related with infinite running repeat function
Item
Setting value
Description
Infinite
running
repeat
position
pulse
1
∼
2147483647[pulse]
mm
1
∼
2147483647[X10
-4
mm]
Inch
1
∼
2147483647[X10
-5
Inch]
degree 1
∼
2147483647[X10
-5
degree]
Sets the repeated position value to be
refreshed automatically.
Infinite
running
repeat
0: Disable
1: Enable
Sets whether to enable Infinite running
repeat function or not.
Infinite running repeat position
0
Содержание XBF-PN04B
Страница 1: ...Programmable Logic Controller Positioning Module EtherCAT XGB Series XBF PN04B XBF PN08B ...
Страница 626: ...Chapter 9 Functions BPS37 setup RS232 and PC connection BPS37 option board LED 9 193 ...
Страница 628: ...Chapter 9 Functions c Execute BPS37 set up program and enter the setting values as follows 9 195 ...
Страница 796: ...Appendix3 Dimension A3 1 Appendix 3 Dimension Appendix 3 1 Dimension of XBF PN04B PN08B ...