Chapter 6 Command
6-9
6.3.4 Indirect start (Command : XIST)
(1) Program
(2) Description
Device
Description
M00003
axis1 indirect start input
U02.00.0
axis1 ready
D00000.0
axis1 in operation
D00000.1
axis1 error state
D01300
axis1 step no.
D00003.9
axis1 servo on signal
D00003.A
axis1 servo error
Comman
d
DST
Indirect start
Operand
OP1
Slot
Constant
WOR
D
Slot No. installed with positioning module
OP2
Axis
PMLK,constant,D,Z,R,ZR WOR
D
Command axis
XBF-PN04B: 1axis~4axis
XBF-PN08B:1axis~8axis
OP3 Operation
step
PMLK,constant,D,Z,R,ZR WOR
D
Step No. to operate (0~400)
※
PMLK means P, M, L and K areas.
(a) If operation step No. is set as “0” in indirect start, it will be operated as current step No. If other number
except 0 is set as the operation step number, it operates only for step no. set.
(b) If operation pattern is set as Continuous or Keep, several steps can be operated by an indirect start command.
(c) D device signal (axis1 in Operation, etc) which used in the example above is an assumption that saving the
axis state value in D device area with XSRD command.