HV100 Series High Performance Current Vector Inverter
50
11.08
Communication
display selection
LED single digit: Display and selection of communication
bus voltage
0: Normal display
1: Magnify 10 times
2: Magnify 100 times
3: Shrink 10 times
4: Shrink 100 times
LED10 digit: Communication current display selection
0: Normal display
1: Magnify 10 times
2: Magnify 100 times
3: Shrink 10 times
4: Shrink 100 times
LED100 digit: Operation frequency display selection
0:Normal display
1: Magnify 10 times
2: Magnify 100 times
3: Shrink 10 times
4: Shrink 100 times
LED1000 digit: Reserved
000
~
444
000
×
012 Group-Advanced functions and performance parameters
Function
code
Name
Content
Setting
range
Factory
Alteration
12.00
Energy
consumption
braking function
setting
0: Invalid
1: Valid throughout
2: Only valid when decelerating
0
~
2
1
×
12.01
Energy
consumption
braking starting
voltage
220V:
340
~
380V
360V
380V:
660
~
760V
680V
Type
setting
○
12.02
Energy
consumption
braking return
difference voltage
220V: 10
~
100V
5V
380V: 10
~
100V
10V
Type
setting
○
12.03
Energy
consumption
braking action
ratio
10
~
100
%
100%
○
12.04
Power failure
restart settings
0: Forbid
1: Starting from starting frequency
2: Speed tracking start
0
~
2
0
×
12.05
Waiting time for
restart after power
failure
During the waiting time for restart, any operation
instruction entered is invalid. If the shutdown command
is input, the inverter will automatically release the speed
tracking restart state and return to the normal shutdown
state.
0.0
~
60.0s
5.0
×