HV100 Series High Performance Current Vector Inverter
67
Tips
:
Acceleration and deceleration time 1 is defined in 00.16 and 00.17.
01.19
Selection of acceleration and deceleration time unit
0
~
2
0
0: Second
1: Minute
2
:
0.1 second
This function code defines the dimension of acceleration and deceleration time.
01.20
Jog forward running frequency setting
0.00 ~ [00.13] upper limit frequency
5.00
01.21
Jog reverse running frequency setting
0.00 ~ [00.13] upper limit frequency
5.00
01.22
Jog acceleration time
0.1
~
3600.0s
Type setting
01.23
Jog deceleration time
0.1
~
3600.0s
Type setting
01.24
Jog Interval time
0.1
~
100.0s
0.1
01.20 ~ 01.24 defines relevant parameters during jog operation. As shown in fig. 01-5, t1 and t3 are the actual jog
acceleration and deceleration time; t2 is JOG time; t4 is jog interval time (01.24); 01 is the running frequency of forward jog
(01.20); f2 is the reverse jog operation frequency (01.21). The actual jog acceleration time t1 is determined according to the
following formula:
t1=01.20*01.22/00.12
Similarly, the actual jog deceleration time t3 can be determined as follows:
t3=01.21*01.23/00.12
Where 00.12 is the maximum output frequency.
Figure 01-5 JOG Operation Diagram
01.25
Jump frequency 1
0.00 ~ upper limit frequency
0.00
01.26
Jump frequency 1 range
0.00 ~ upper limit frequency
0.00
01.27
Jump frequency 2
0.00 ~ upper limit frequency
0.00
01.28
Jump frequency 2 range
0.00 ~ upper limit frequency
0.00
01.29
Jump frequency 3
0.00 ~ upper limit frequency
0.00
01.30
Jump frequency 3 range
0.00 ~ upper limit frequency
0.00
Time
Output
Reverse jog command
Forward jog command