HV100 Series High Performance Current Vector Inverter
48
10.24
Selection of
RS485
communication
abnormal action
0: Protection action and free stop
1: Alarm and maintain the status to continue operation
2: Alarm and stop according to the stop mode
0
~
2
1
×
10.25
RS485
communication
timeout detection
time
If RS485 communication fails to receive the correct data
signal within the time interval defined by this function
code, it is considered that RS485 communication is
abnormal, and the inverter will make corresponding
actions according to the setting of 10.24. When this value
is set to 0.0, RS485 communication timeout detection is
not performed.
0.0
~
100.0s
0.0
○
10.26
Keypad
communication
abnormal action
selection
0: Protection action and free stop
1: Alarm and maintain the status to continue operation
2: Alarm and stop according to the stop mode
0
~
2
1
×
10.27
Keypad
communication
timeout check-out
time
If the keypad communication fails to receive the correct
data signal within the time interval defined by this
function code, it is considered that the keypad
communication is abnormal, and the inverter will make
corresponding actions according to the setting of 10.26.
0.0
~
100.0s
1.0
○
10.28
EEFROM reading
and writing error
action selection
0: Protection action and free stop
1: Alarm and maintain the status to continue operation
0
~
1
0
×
10.29
Motor overload
protection
threshold
When the 10.00 bit is set to 3, the output current reaches
the motor overload protection threshold (10.29), and then
delays the motor overload protection detection time
(10.30) and reports the motor overload E-08.
0
~
200%*
Motor rated
current
150%
×
10.30
Motor overload
protection
detection time
0
~
60000S
100
○
10.31
Inverter overload
protection
threshold
When 10.00 bit is 2, the output current reaches the
overload protection threshold of inverter (10.31), and
then delays the overload protection detection time of
inverter (10.32), and then reports the overload of inverter
E-09.
0
~
200%*
INV rated
current
150%
×
10.32
Inverter overload
protection
detection time
0
~
60000S
60
○
10.33
OC and module
fault limit reset
times
When the failure times of OC and module exceed this set
value, it needs to be powered on again before resetting.
0
~
9999
5
○
10.34
Selection of
encoder frequency
adjustment start
bit
0: LED units
1: LED tens
2: LED hundreds
3: LED thousands
0
~
3
0
○
10.35
Reserved
—
—
0
◆
011Group-RS485 communication parameters
Function
code
Name
Content
Setting
range
Factory
Alteration
11.00
Protocol selection
0: MODBUS
1: User defined
0
~
1
0
×
11.01
Local address
0: Broadcast address
1
~
247: Slave station
0
~
247
1
×
11.02
Communication
baud rate setting
0: 2400BPS
1: 4800BPS
2: 9600BPS
3: 19200BPS
4: 38400BPS
5: 115200BPS
0
~
5
3
×