HV100 Series High Performance Current Vector Inverter
54
14.02
STOP+RUN key
emergency
stop
function
0: Forbid
1: Free stop
0
~
1
1
○
14.03
Closed
loop
display coefficient
This function code is used to correct the display error
between the actual physical quantity (pressure, flow,
etc.) and the given or feedback quantity (voltage,
current) during closed-loop control, and has no influence
on closed-loop adjustment.
0.01
~
100.00
1.00
○
14.04
Load
speed
display coefficient
This function code is used to correct the display error of
speed scale, and has no influence on the actual speed.
0.01
~
100.00
1.00
○
14.05
Line
speed
coefficient
This function code is used to correct the display error of
linear speed scale, and has no influence on the actual
speed.
0.01
~
100.00
1.00
○
14.06
Encoder
adjustment rate
The larger the value, the faster the encoder adjusts
1
~
100
70
○
14.07
Monitoring
parameter
selection 1 in
running state
(main display)
The monitoring items of the main monitoring interface
can be changed by changing the set values of the above
function codes. For example, if 14.07=5, that is, the
output current d-05 is selected, the default display item of
the main monitoring interface is the current output
current value during operation.
0
~
57
0
○
14.08
Monitoring
parameter
selection 2 in
running state
(Auxiliary display)
0
~
57
5
○
14.09
Monitoring
parameter
selection 1 in stop
state (main
display)
The monitoring items of the main monitoring interface
can be changed by changing the set values of the above
function codes. For example, if 14.09=6, that is, the
output voltage d-06 is selected, the default display item
of the main monitoring interface will be the current output
voltage value when the machine stops.
0
~
57
1
○
14.10
Monitoring
parameter
selection 2 in stop
state (Auxiliary
display)
0
~
57
13
○
14.11
Parameter display
mode selection
LED ones: function parameter display mode selection
0: display all function parameters
1: only display the parameters that are different from the
factory value
2: only display the parameters modified after the last
power-on (reserved)
LED ten digits: monitor parameter display mode
selection
0: only display main monitor parameters
1: Main and auxiliary display alternately (interval time 1s)
LED hundreds: adjust frequency display selection
0: display frequency
1: Only display status monitoring parameters
Thousands of LED: Panel
▲
/
▼
key adjustment enable
0: Valid
1: invalid
0000
~
1112
0100
○
14.12
Parameter
initialization
0: No operation
1: All parameters except motor parameters are restored
to factory settings
2: Restore all user parameters to factory settings
3: Clear fault record
0
~
3
0
×
14.13
Parameter protect
0: Modify all Parameter (Some parameters cannot be
modified during operation)
1: only the frequency settings 00.07 and 00.10 and this
function code can be modified
2: All parameters except this function code are forbidden
to be modified
Note: the above restrictions are invalid for this function
code and 14.13
0
~
2
0
○