HV100 Series High Performance Current Vector Inverter
55
14.14
Parameter copy
0: No operation
1: Upload parameters to the keypad
2: Download all function code parameters to the inverter
3: Download all function code parameters except motor
parameters to the inverter
Note 1: When selecting parameter download, the
software will judge whether the inverter power
specifications are consistent. If they are inconsistent, the
parameters related to the model will not be modified.
Note 2: Only the external keyboard KB2 has the copy
function, and the normal keyboard copy will prompt an
error.
0
~
3
0
×
14.15
Software version
14.15
~
14.16 View only, cannot be modified.
1.00
~
99.99
4.12
◆
14.16
Keypad version
1.00
~
99.99
1.00
◆
14.17
INV rated power
This parameter can only be viewed and cannot be
modified.
0.4
~
999.9KW
(
G/P)
Type
setting
◆
14.18
Inverter
type
selection
0: G type (constant torque load model)
1: P type (load type of fan and water pump)
Note 1: After setting as P type machine, the motor
parameters will be refreshed automatically, and it can be
used as a higher gear special frequency converter for fan
and water pump without changing any parameters.
Note 2: This parameter cannot be initialized, please
modify it manually
0
~
1
0
×
015 Group-Multiple pumps water supply parameters
Function
code
Name
Content
Setting
range
Factory
Alteration
15.00
Terminal
delay
time
The delay time when the pump is switched on and off.
0.0
~
600.0s
0.1
○
15.01
Polling time
Polling time is the time to switch the variable frequency
pump regularly, which is only valid when a single pump
works.
0.0
~
600.0h
48.0
○
15.02
Lower limit
frequency for
reducing the
number of pumps
When the feedback pressure is higher than the set
pressure and the frequency drops to the lower limit
frequency of pump reduction, the pump is reduced after
the delay time of pump reduction.
0.0
~
600.00HZ
35.00
×
15.03
Main pump
Start-up delay time
This parameter is used in the "one drive three constant
pressure water supply", the main pump start delay time
after the main and auxiliary pumps are switched.
0.0
~
3600.0s
0.0
○
15.04
Auxiliary pump
Start-up mode
0: Direct start
1: Soft start
0
~
1
0
×
15.05
Add pump delay
time
The delay time used for adding the pump,
0.0
~
3600.0s
10.0
○
15.06
Reduce
pump
delay time
The delay time used for reduce the pump,
0.0
~
3600.0s
10.0
○
15.07
Sensor range
If 08.01=5, select the sensor range (15.07) and the given
pressure (15.08) according to the field conditions.
0.00
~
60.00
(
MPa
、
Kg
)
10.00
○
15.08
Pressure setting
0.00
~
【
15.07
】
(
MPa
、
Kg
)
5.00
○
016 Group-Photovoltaic water pump MPPT parameters