HV100 Series High Performance Current Vector Inverter
114
0: protection action and free stop
1: Protect actions and maintain the status quo to continue running
2: Protection action and shutdown according to the set shutdown mode
10.27
Keypad communication timeout check-out time
0.0
~
100.0s
1.0
If the keypad communication fails to receive the correct data signal within the time interval defined by this function
code, it is considered that the keypad communication is abnormal, and the inverter will make corresponding actions
according to the setting of 10.26.
10.28
EEFROM reading and writing error action selection
0
~
1
0
0: protection action and free stop
1: Alarm and continue running
10.29
Motor overload protection threshold
0 ~ 200% * rated current of motor
150%
10.30
Motor overload protection detection time
0
~
60000S
100
When 10.00 ten bits are 2, the output current reaches the overload protection threshold of the inverter (10.31), and
then delays the overload protection detection time of the inverter (10.32), and then reports the overload of the inverter E-09.
10.31
Inverter overload protection threshold
0 ~ 200% * rated current of inverter
150%
10.32
Inverter overload protection detection time
0
~
60000S
60
When 10.00 ten bits are 2, the output current reaches the overload protection threshold of the inverter (10.31), and
then delays the overload protection detection time of the inverter (10.32), and then reports the overload of the inverter E-09.
10.33
OC and module fault limit reset times
0
~
9999
5
When the failure times of OC and module exceed this set value, it needs to be powered on again before resetting.
10.34
Selection of encoder frequency modulation start bit
0
~
3
1
0: LED bits
1: LED ten bits
2:LED hundred bits
3: LED thousand bits
10.35
Reserved
0
0
011 Group-RS485 communication parameters
11.00
Protocol selection
0
~
1
0
Communication protocol selection
0:MODBUS
1:Automatic
11.01
Local address
0
~
247
1
0: Broadcast address
1
~
247:Slave station