HV100 Series High Performance Current Vector Inverter
64
Group 01-start-stop control parameters
01.00
Starting mode
0
~
2
0
0: Starting frequency starting
Start according to the set starting frequency (01.01 ) and starting frequency holding time (01.02 ).
1: DC starting frequency starting
First DC brake (refer to 01.03 and 01.04), and then start according to mode 0.
2. Speed tracking starting
In case of power-on after power failure, if the starting conditions are met, the inverter will automatically start running in
the mode of speed tracking after waiting for the time defined in 12.15.
01.01
Starting frequency
0.00
~
50.00Hz
1.00
01.02
Starting frequency holding time
0.0
~
600.0s
0.0
Starting frequency refers to the initial frequency when the inverter starts. As shown in the figure fs below, for some
systems with large starting torque, setting reasonable starting frequency can validly overcome the problem of starting
difficulty. The starting frequency holding time refers to the time that the inverter keeps running at the starting frequency
during the starting process, as shown in the figure below at t1. Schematic diagram of startup frequency is as follows:
Figure 01-1 Diagram of Start Frequency
Tips
:
1
、
The start frequency is not limited by the lower limit frequency. The JOG frequency is not limited by the lower limit
frequency but is limited by the starting frequency.
2. When 00.15=1 (high frequency mode), the upper limit of starting frequency is 500.0Hz.
01.03
Starting DC braking current
0.0 ~ 150.0% * rated current of motor
0.0%
01.04
Starting DC braking time
0.0
~
100.0s
0.0
The starting DC braking current is set as a percentage relative to the rated output current of the inverter.
When starting DC braking time is 0.0s, there is no DC braking process. As shown in the figure below:
Time