HV100 Series High Performance Current Vector Inverter
75
Vmax:
Maximum output voltage
Fb:
Maximum output frequency
Fig. F5-1 V/F curve diagram
05.01
Torque boost setting
0.0 ~ 30.0% rated Voltage of motor
Model setting
05.02
Torque boost cutoff frequency
0.0
~
Motor rated Power
15.00
In order to compensate for the low-frequency torque characteristics, some boost compensation can be made for the
output voltage. When this function code is set to 0.0%, it is automatic torque lifting, and when any value is not 0.0%, it is
manual torque lifting mode. 05.02 defines the lifting cut-off frequency point fz when manual torque lifting is performed, as
shown in Figure F5-2.
Vb- manual torque increase
Figure F5-2 Schematic diagram of torque boost
Notes:
1
:
Under normal V/F control mode, automatic torque boost mode is invalid.
2
:
Automatic torque boost is only valid in advanced V/F control mode.
05.03
V/F frequency value F1
0.00
~
Frequency value F2
12.50
05.04
V/F Voltage V1
0.0 ~ voltage value V2
25.0%
Output
voltage
Output
frequency