HV100 Series High Performance Current Vector Inverter
91
07.12
UF/DOWN terminal frequency modification rate
0.01
~
50.00Hz/S
1.00
This function code is the frequency modification rate when setting the frequency of the UP/DOWN terminal, that is,
the amount of frequency change, when the UP/DOWN terminal is short-circuited with the COM terminal for one second;
When 00.18=1 (high frequency mode), the maximum value of this function code is 500.0 Hz/s.
07.13
Reservation
—
0
07.14
Y1 output delay time
0.0
~
100.0S
0.0
07.15
Y2 output delay time
0.0
~
100.0S
0.0
07.16
R1 output delay time
0.0
~
100.0S
0.0
07.17
R2 output delay time
0.0
~
100.0S
0.0
This function code defines the delay from the change of digital output terminal and relay state to the output change.
07.18
Open collector output terminal Y1 is set
0
~
62
0
07.19
Open collector output terminal Y2 is set
0
~
62
0
07.20
Output of programmable relay R1
0
~
62
3
07.21
Output of programmable relay R2
0
~
62
0
0
:
None
1: The inverter runs forward
When the inverter is in the forward running state, output indication signal.
2
:
Inverter reverse operation
When the inverter is in reverse operation state, output indication signal.
3
:
Fault output
When the inverter fails, output indication signal.
4: Frequency/speed level detection signal (FDT1)
Refer to 07.24 ~ 07.26 parameter function description.
5: Frequency/speed level detection signal (FDT2)
Refer to 07.27 ~ 07.29 parameter function description.
6: Frequency/Speed Arrival Signal (FAR)
Refer to 07.23 Parameter Function Description.
7
:
Indication in zero speed running of inverter
The output frequency of the inverter is 0.00Hz, but it is still in the running state.
8
:
Output frequency reaches upper limit
When the output frequency of the inverter reaches the upper limit frequency, output indication signal.
9
:
Output frequency reaches lower limit
When the output frequency of the inverter reaches the lower limit frequency, output indication signal.
10
:
The set lower limit of frequency reaches in running time
When the inverter is running, if the set frequency is less than or equal to the lower limit frequency, output an indication
signal.
11
:
Inverter overload pre-alarm signal
When the output current of the inverter exceeds the overload pre-alarm level (10.12), the indicator signal is output after
the alarm delay time (10.13). Commonly used for overload pre-alarm.