HV100 Series High Performance Current Vector Inverter
102
RUN command
Fig. F9-2 Schematic diagram of PLC maintenance after single cycle
2: Finite continuous cycle
The inverter determines the cycle times of PLC operation according to the limited number of continuous cycles set in
09.04, and stops when the cycle times are reached. 09.04=0, the inverter is not running.
3
:
Continuous circulation
After completing one cycle, the inverter will automatically start the next cycle, and will not stop until there is a stop
command. As shown in the figure below:
RUN command
Figure F9-3 Schematic diagram of PLC continuous cycle
09.01
Operation mode of PLC
0
~
1
0
0
:
Automatic
1: Manually operation through the defined multi-function terminal
09.02
Memory of PLC running power failure
0
~
1
0
0: Not store
Do not remember the PLC running state when power is cut off, and restart after power-on to start running from the first
section.
1
:
Remember the stage and frequency of power-down time
Memorize PLC running state when power is cut off, including power-off time stage, running frequency and running time.
Start again after power-on, automatically enter this stage, and continue to run for the rest of the time at the frequency
defined by this stage.
09.03
PLC starting mode
0
~
2
0
PLC command
Second cycle
First cycle