HV100 Series High Performance Current Vector Inverter
7
Analog output
2 analog signals are output, and the output range can be
flexibly set between 0 ~ 20mA or 0 ~ 10V, which can
realize the output of physical quantities such as set
frequency and output frequency
Automatic voltage
stabilizing
operation
According to the needs, three modes can be selected: dynamic voltage stabilization,
static voltage stabilization and non-voltage stabilization, so as to obtain the most
stable operation effect
Acceleration and
deceleration
Time setting
0.1s
~
3600.0min can be set continuously, and S-type and linear mode can be
selected
Bra
ke
Energy
consumpti
on
Brake
Energy consumption braking starting voltage, return difference voltage and energy
consumption braking rate can be continuously adjusted
Direct
current
Brake
Starting frequency of DC braking during shutdown: 0.00 ~ [00.13] upper limit
frequency
Braking time: 0.0 ~ 100.0 s; Braking current: 0.0% ~ 150.0% rated current
Magnetic
flow
Brake
0 ~ 100 0: invalid
Low noise
operation
The carrier frequency is continuously adjustable from 1.0 kHz to 16.0 kHz to minimize
the noise of the motor
Revolving speed
tracking speed
Restart facility
It can realize the smooth restart and instantaneous stop restart of the motor in
operation
Counter
One internal counter is convenient for system integration
Operating function
Upper and lower limit frequency setting, frequency jump operation, reverse operation
limit, slip frequency compensation, RS485 communication, frequency increment and
decrement control, fault self-recovery operation, etc
Display
keypad
display
Running
State
Output frequency, output current, output voltage, motor speed, set
frequency, module temperature, PID setting, feedback amount,
analog input and output, etc
Alarm
Content
The last six fault records, the record of six operation parameters such as output
frequency, set frequency, output current, output voltage, DC voltage and module
temperature during the last fault trip.
Protection function
Over-current, over-voltage, under-voltage, module failure, electronic thermal relay,
overheating, short circuit, input and output phase failure, abnormal tuning of motor
parameters, internal memory failure, etc.
Environ
ment
Ambient
temperature
-10
℃
~+40
℃
(the ambient temperature is 40
℃
~ 50
℃
, please use it at a reduced
level)
Ambient humidity
5% ~ 95% RH, no water condensation
Surrounding
environment
Indoor (no direct sunlight, corrosion, flammable gas, oil mist, dust, etc.)
Altitude
1000 meters above the use of derating, every 1000 meters up derating 10%
Structu
re
Protection grade
IP20
Cooling mode
Air-cooled with fan control
Installation method
Wall mounted, cabinet mounted