HV100 Series High Performance Current Vector Inverter
140
Appendix 2: Description of macro parameter setting
Functional
macro
definition
Setting
parameters
Automatically modify
parameter list
Commissioning steps
Single pump
constant
pressure water
supply mode
00.01=1
00.04=8
;
08.01=5
;
14.07=42
;
14.08=40
;
14.09=42
;
14.10=40
。
Step1
:
Initialization of parameter settings
(
14.12=2
);
Step2: Function macro selection (00.01 = 1);
Step3: Set the sensor range (15.07);
Step4: Determine the feedback type of the sensor,
and input the voltage feedback signal by default for
AI1 and AI2, or select the input current feedback
signal for AI1 through the jumper seat JP3;
Step5: Set the target pressure, which can be set by
parameter 15.08 or by keyboard up and down
keys.
One inverter
with two
working (1
variable
frequency
pump +2
power
frequency
pumps) water
supply mode
00.01=2
00.03=1
;
00.04=8
;
08.01=5
;
14.07=42
;
14.08=40
;
14.09=42
;
14.10=40
;
07.00=58
;
07.01=59
;
07.02=60
;
07.03=61
;
07.04=62
;
07.05=63
;
07.18=59
;
07.19=60
;
07.20=61
。
Step1
:
Initialization of parameter settings
(
14.12=2
);
Step2
:
Function macro selection
(
00.01=2 or 3
);
Step3: Set the sensor range (15.07);
Step4: Determine the feedback type of the sensor,
and input the voltage feedback signal by default for
AI1 and AI2, or select the input current feedback
signal for AI1 through the jumper seat JP3;
Step5: Set target pressure, which can be set by
parameter 15.08, or by keyboard up and down
keys;
Step6: For details, refer to the description of water
supply parameters for soft start-up of three pumps.
Three-pump
cycle soft start
(3 variable
frequency
pumps) water
supply mode
00.01=3
Water supply
mode of
photovoltaic
pump
00.01=4
00.03=1
;
00.04=10
;
16.00=0
;
16.04=0.00
;
12.13=80
。
Step1
:
Initialization of parameter settings
(
14.12=2
);
Step2
:
Function macro selection
(
00.01=4
)
.
Control mode
of NC machine
tool
00.01=5
00.02=2
;
00.03=1
;
00.04=3
;
00.12=80.00
;
00.13=80.00
;
00.16=0.5
;
00.17=2.0
。
Step1
:
Initialization of parameter settings
(
14.12=2
);
Step2
:
Function macro selection
(
00.01=5
)
.
Fire patrol
mode
00.01=6
00.02=0
;
00.03=1
;
00.16=80.00
;
01.08=1
;
02.03=2950
;
05.00=5
;
05.01=2.0
;
05.03=1.25
;
05.04=2.0
;
05.05=5.00
;
05.06=15.0
;
05.07=50.00
;
05.08=100.0
;
10.01=120.0
;
10.06=200
;
10.12=180
。
Step1
:
Initialization of parameter settings
(
14.12=2
);
Step2
:
Function macro selection
(
00.01=6
)
.
EPS power
mode
00.01=7
00.02=4
;
05.12=0
;
05.17=100.0
;
12.19=002.
Step1
:
Initialization of parameter settings
(
14.12=2
);
Step2
:
Function macro selection
(
00.01=7
)
.