HV100 Series High Performance Current Vector Inverter
121
1:It can be reset after the power supply is normal
LED thousand bits: Reserved
12.26
Upper limit frequency of oscillation suppression
0.00
~
300.00Hz
50.00
12.27
Oscillation suppression coefficient
1
~
500
50
12.28
Oscillation suppression voltage
0.0 ~ 25.0% * rated Voltage of motor
5.0
12.27
~
12.28 Please refer to the description of 12.19 for details.
12.29
Wave-by-wave current limiting and anti-overvoltage action selection
0000
~
1111
011
LED bits: Selection of wave by wave current limiting acceleration
0: Invalid
1: Valid
LED ten bits: Selection of wave by wave current limiting deceleration
0: Invalid
1: Valid
LED hundred-bit: Selection of wave by wave current limiting and constant speed
0: Invalid
1: Valid
LED Thousand bits: Selection of anti overvoltage action
0: Invalid
1: Valid
12.30
Special function selection
00
~
11
00
LED bits: Direct-Start function select
0: Invalid
1: Valid
This function is only valid when running at constant speed.
LED Ten bits: Display selection of over-torque alarm A-05
0: Display
1: Do not display
LED hundred bits: Reserved
LED thousand bits: Reserved
013 Group-Reserved parameters
014 Group-Panel function setting and parameter management
14.00
M-FUNC function selection
0
~
4
0
0: JOG (jog control)
The
M-FUNC
key is jog control, and the default direction is determined by 00.18.
1: Forward/Reverse rotation switch
In the running state, the
M-FUNC
key is equivalent to the direction switch key, and pressing this key in the shutdown
state is invalid. This switch is only valid for the panel run command channel.
2: Clear the panel
key to set the frequency
3: Switching between local operation and remote operation (reserved)
4: Reverse
At this time, the
M-FUNC
key can be directly used as the reverse key to control the reverse operation of the motor.