HV100 Series High Performance Current Vector Inverter
27
01.32
Stop delay time
when frequency is
lower than lower
limit frequency
(Simple
dormancy)
Set stop delay time when frequency is lower than
lower limit frequency (Simple dormancy)
0.0
~
3600.0s
10.0
○
01.33
Zero frequency
braking current
This parameter is the percentage of the rated current
of the motor.
0.0
~
150.0%*Rated
current
0.0
×
01.34
Forward and
reverse dead zone
time
The waiting time for a inverter to transition from
forward operation to reverse operation, or from
reverse operation to forward operation.
0.0
~
100.0s
0.0
○
01.35
Forward and
reverse switching
mode
0: Over 0Hz frequency switching
1: Over start frequency switching
0
~
1
0
×
01.36
Emergency stop
standby
deceleration time
It is only valid for function No.10 in digital input
terminal (07.00 ~ 07.06).
0.1
~
3600.0s
1.0
○
01.37
Current holding
time for DC
braking during
shutdown
Set Current holding time for DC braking during
shutdown
0.0
~
100.0s
0.0
○
002 group-Motor Parameters
Function
code
Name
Content
Setting range
Factory
Alteration
02.00
Selection of motor
type
0: AC asynchronous motor
1: Reserved
Note: This parameter cannot be initialized, please
modify it manually
0
~
1
0
×
02.01
Motor rated
power
Set according to the parameters of motor nameplate.
Please configure the corresponding motor according
to the power of the inverter. If the power difference is
too large, the control performance of the inverter will
obviously decrease.
0.4
~
999.9KW
Model
setting
×
02.02
Motor rated
frequency
0.01Hz
~
【
00.13
】
50.00
×
02.03
Motor rated
rotating speed
0
~
60000RPM
Model
setting
×
02.04
Motor rated
Voltage
0
~
999V
Model
setting
×
02.05
Motor rated
current
0.1
~
6553.5A
Model
setting
×
02.06
Stator resistance
of asynchronous
motor
If the motor is tuned, the set values from 02.06 to
02.10 will be updated after the tuning is finished.
0.01
~
20.000Ω
Model
setting
×
02.07
Rotor resistance of
asynchronous
motor
0.01
~
20.000Ω
Model
setting
×
02.08
Inductance of
stator and rotor of
asynchronous
motor
0.1
~
6553.5mH
Model
setting
×
02.09
Mutual inductance
between stator
and rotor of
asynchronous
motor
0.1
~
6553.5mH
Model
setting
×
02.10
No-load current of
asynchronous
motor
0.01
~
655.35A
Model
setting
×