HV100 Series High Performance Current Vector Inverter
141
Appendix 3: Parameter description of soft start water supply of three
pump circulation
Function
code
Name
Setting range
Minimum
unit
Factory
setting
Change
00.01
Multi-pump water
supply mode selection
0: invalid
2
: (
1 set of frequency conversion
pump +2 sets of power frequency
pump
)
3
:
Three pump circulation soft start (3
frequency conversion pumps
)
1
0
×
00.03
Run command channel
selection
1: terminal operation command
channel
1
0
×
00.04
Main frequency source
selection
8: PID control setting
1
0
×
07.00
Input terminal DI1
function
33. PID control input
58: Start/stop (manual)
59: Operation allowed
60: Interlock 1
61: Interlock 2
62: Interlock 3
63
:
PFC start/stop
1
58
×
07.01
Input terminal DI2
function
1
59
×
07.02
Input terminal DI3
function
1
60
×
07.03
Input terminal DI4
function
1
61
×
07.04
Input terminal DI5
function
1
62
×
07.05
Input terminal DI6
function
1
63
×
07.06
Input terminal HDI
function
1
0
×
07.18
Open collector output
terminal Y1 is set
59: Interlock 1 output
60: Interlock 2 Output
61: Interlock 3 Output
1
59
×
07.19
Open collector output
terminal Y2 setting
1
60
×
07.20
Output of
programmable relay
R1
1
61
×
07.21
Programmable relay
R2 output
1
0
×
08.00
Operation input mode
of PID
0
:
Automatic
1: manually input through the defined
multi-function terminal
1
0
×
08.01
PID given channel
selection
0
:
number given
1
:
AI1
2
:
AI2
3: Pulse given
4: RS485 communication
1
0
○
08.02
Given the digital
quantity setting
0.0
~
100.0%
0.1%
50.0%
○
08.03
Selection of PID
feedback channel
0
:
AI1
1
:
AI2
2
:
AI1+ AI2
3
:
AI1-AI2
4
:
MAX
{
AI1
,
AI2
}
5
:
MIN
{
AI1
,
AI2
}
6: Pulse given
7: RS485 communication
1
0
○
08.04
Advanced
characteristic setting of
PID controller
LED bit: PID polarity selection 0:
positive 1: negative
LED ten bits: proportional adjustment
characteristic 0: constant proportional
integral adjustment
1
:
automatic variable proportion
integral adjustment LED hundred bits:
integral adjustment characteristic 0:
when the frequency reaches the
upper and lower limits, stop integral
adjustment
1: when the frequency reaches the
upper and lower limits, continue
integral adjustment
LED thousand bits: reservation
1
000
×