HV100 Series High Performance Current Vector Inverter
122
14.01
Selection of STOP/RST key function
0
~
3
3
0: Only valid for panel control
Only when 00.04=0, this key can control the inverter to stop.
1: Valid for both panel and terminal control
Only when 00.04=0 or 1, this key can control the inverter to stop. In the communication control operation mode, this
key is invalid.
2:Valid for panel and communication control at the same time
Only when 00.04=0 or 2, this key can control the inverter to stop. In terminal control operation mode, this key is invalid.
3: Valid for all control modes
In any operation command channel mode, this key can control the inverter to stop.
Tips:
In any operation command channel mode, the reset function is valid .
14.02
STOP key +RUN key emergency stop function
0
~
1
1
0: Invalid
1: Free stop
Press the
RUN
key and the
S T O P / R E S E T
key at the same time, and the inverter will stop freely.
14.03
Closed loop display coefficient
0.01
~
100.00
1.00
This function code is used to correct the display error between the actual physical quantity (pressure, flow, etc.) and
the given or feedback quantity (voltage, current) during closed-loop control, and has no influence on closed-loop
adjustment.
14.04
Load speed display coefficient
0.01
~
100.00
1.00
This function code is used to correct the display error of speed scale, and has no influence on the actual speed.
14.05
Line speed coefficient
0.01
~
100.00
1.00
This function code is used to correct the display error of linear speed scale, and has no influence on the actual speed.
14.06
Encoder adjustment rate
1
~
100
70
14.07
Monitoring parameter selection 1 in running state (main display)
0
~
57
0
14.08
Monitoring parameter selection 2 in running state (Auxiliary display)
0
~
57
5
The monitoring items of the main monitoring interface can be changed by changing the set values of the above
function codes. For example, if 14.08=5, that is, the output current d-05 is selected, the default display item of the main
monitoring interface is the current output current value during operation.
14.09
Monitoring parameter selection 1 in stop state (main display)
0
~
57
1
14.10
Monitoring parameter selection 2 in stop state (main display)
0
~
57
12
The monitoring items of the main monitoring interface can be changed by changing the set values of the above
function codes. For example, if 14.10=6, that is, the output voltage d-06 is selected, the default display item of the main
monitoring interface will be the current output voltage value when the machine stops.