HV100 Series High Performance Current Vector Inverter
45
09.55
Swing frequency
control
0: Invalid
1: Effective
0
~
1
0
×
09.56
Swing frequency
operation mode
0: Automatic
1: Manually operation through the defined multi-function
terminal
0
~
1
0
×
09.57
Swing amplitude
control
0: Fixed swing
1:Variable swing
0
~
1
0
×
09.58
Swing frequency
stop/starting mode
selection
0: Start according to the state memorized before
stopping
1: Restart
0
~
1
0
×
09.59
Power-down
storage of
frequency swing
state
0: Store
1: Not store
0
~
1
0
×
09.60
Swing preset
frequency
The frequency at which the frequency converter operates
before it enters the swing operation mode or when it
leaves the swing operation mode and the time it runs at
this frequency point. If the function code 09.61≠0 (swing
frequency preset frequency waiting time) is set, the
inverter directly enters the swing frequency preset
frequency operation after starting, and enters the swing
frequency mode after the swing frequency preset
frequency waiting time.
0.00Hz
~
Upper limit
frequency
10.00
○
09.61
Swing preset
frequency waiting
time
0.0
~
3600.0s
0.0
×
09.62
Swing amplitude
The amplitude of Swing frequency is determined by
09.62, and the operating frequency of swing frequency is
restricted by the upper and lower frequencies. If it is set
improperly, the Swing frequency will not work normally.
0.0
~
100.0
%
0.0%
○
09.63
Jump frequency
This function code refers to the amplitude of rapid
decline after the frequency reaches the upper limit
frequency of the swing frequency, and of course it also
refers to the amplitude of rapid rise after the frequency
reaches the lower limit frequency of the swing frequency.
If it is set to 0.0%, there is no sudden jump frequency.
0.0
~
50.0
%
(Relative
swing
frequency
amplitude)
0.0%
○
09.64
Swing frequency
rise time
This function code defines the running time from the
lower limit frequency to the upper limit frequency and
from the upper limit frequency to the lower limit
frequency.
0.1
~
3600.0s
5.0
○
09.65
Swing frequency
falling time
0.1
~
3600.0s
5.0
○
09.66
Reserved
—
—
0
◆
09.67
Fixed length
control
0: Invalid
1: Effective
0
~
1
0
×
09.68
Set length
This set of functions is used to realize the fixed-length
shutdown function.
The frequency converter inputs counting pulses from the
terminal (HDI defined as function 47 ), and obtains the
calculated length according to the number of pulses per
revolution of the speed measuring shaft (09.73 ) and the
circumference of the shaft (09.72 ).
Calculation length = count pulse number ÷ Number of
pulses per revolution × Measure the circumference of
shaft.
The calculated length is corrected by length
magnification (09.70) and length correction coefficient
(09.71), and the actual length is obtained.
0.000
~
65.535(KM)
0.000
○
09.69
Actual length
0.000
~
65.535(KM)
0.000
○
09.70
Length
magnification
0.100
~
30.000
1.000
○
09.71
Length correction
coefficient
0.01
~
1.000
1.000
○