HV100 Series High Performance Current Vector Inverter
32
05.24
Limiting voltage of
voltage feedback
disconnection
This voltage represents the output voltage of the
inverter, and setting this parameter reasonably can
prevent equipment damage caused by voltage
overshoot at the time of disconnection.
0.0
~
100.0
%
*
rated volt
80.0%
○
05.25
DC Bus
undervoltage
detection value
If DC bus voltage less than the parameter value,the
system will report "E-34".
If the parameter value set 0, the function is invalid.
0
~
1000V
0
○
05.26
Reset DC Bus
undervoltage fault
If DC bus voltage is the equals of the parameter
value,the system will reset the fault "E-34"and run
automatically.
0
~
1000V
0
○
006 group-Analog and pulse input and output parameters
Function
code
Name
Content
Setting
range
Factory
Alteration
06.00
AI1 input
corresponding
physical quantity
0: Speed command
(
output frequency
,
-100.0%
~
100.0%
)
1: Torque command
(
output torque
,
-200.0%
~
200.0%
)
2: Voltage command
(
output voltage, 0.0%
~
200.0%*
Rated voltage
)
0
~
2
0
×
06.01
AI1 input lower
limit
Set AI1 lower limit
0.00V/0.00m
A
~
10.00V/20.0
0mA
0.00
○
06.02
AI1 lower limit
corresponds to
physical quantity
setting
Set AI1 lower limit corresponding setting, which
corresponds to the percentage of upper limit frequency.
-200.0%
~
200.0%
0.0%
○
06.03
AI1 input upper
limit
Set AI1 upper limit
0.00V/0.00m
A
~
10.00V/20.0
0mA
10.00
○
06.04
AI1 upper limit
corresponds to
physical quantity
setting
Set AI1 upper limit corresponding setting, which
corresponds to the percentage of upper limit frequency.
-200.0%
~
200.0%
100.0%
○
06.05
AI1 input Filter
time
Set AI1 Filter time
0.00S
~
10.00S
0.05
○
06.06
AI2 input
corresponding
physical quantity
0: Speed command
(
output frequency
,
-100.0%
~
100.0%
)
1: Torque command
(
output torque
,
-200.0%
~
200.0%
)
2: Voltage command
(
output voltage
,
0.0%
~
200.0%*
Rated voltage
)
0
~
2
0
×
06.07
AI2 input lower
limit
Set AI2 lower limit
0.00V
~
10.00V
0.00
○
06.08
AI2 lower limit
corresponds to
physical quantity
setting
Set AI2 lower limit corresponding setting, which
corresponds to the percentage of upper limit frequency.
-200.0%
~
200.0%
0.0%
○
06.09
AI2 input upper
limit
Set AI2 upper limit
0.00V
~
10.00V
10.00
○
06.10
AI2 upper limit
corresponds to
physical quantity
setting
Set AI2 upper limit corresponding setting, which
corresponds to the percentage of upper limit frequency.
-200.0%
~
200.0%
100.0%
○
06.11
AI2 input Filter
time
Set AI2 Filter time
0.00S
~
10.00S
0.05
○