HV100 Series High Performance Current Vector Inverter
89
0: the terminal operation command is invalid when power-on
In the process of power-on, even if the inverter detects that the operation command terminal is valid (closed), the
inverter will not start. Only when the terminal is closed again after disconnection can the inverter start.
1: the terminal operation command is valid when power on
In the process of power-on, the inverter can start when it detects that the terminal operation command terminal is valid
(closed).
07.10
Input terminal valid logic setting (DI1
~
HDI)
0
~
7FH
00
Ten bits
bit
0: Positive logic, that is, the connection between Xi terminal and common terminal is valid, and the disconnection is invalid
1: Anti-logic, that is, the connection between Xi terminal and common terminal is invalid, and the disconnection is valid
07.11
FWD/REV terminal control mode
0
~
3
0
This function code defines four different ways to control the running of inverter through external terminals.
0: Two-wire control mode 1
Xm: forward command (FWD), Xn: reverse command (REV), Xm and Xn represent any two terminals respectively
defined as FWD and REV functions in DI1-HDI. In this control mode, K1 and K2 can independently control the running and
direction of the inverter
K1
K2
Xm
(
FWD)
Xn(REV)
COM
Figure F7-2 Schematic diagram of two-wire control mode 1
Bit4:DI5 terminal positive and negative
logic definition
Bit5:DI6 terminal positive and negative
logic definition
Bit6: HDI terminal positive and negative
logic definition
Bit7: reservation
Bit0:DI1 terminal positive and negative
logic definition
Bit1:DI2 terminal positive and negative
logic definition
Bit2:DI3 terminal positive and negative
logic definition
Bit3:DI1 terminal positive and negative
logic definition
K2
K1
Running
instructions
0
0
Stop
0
1
Forward
1
0
Stop
1
1
Reverse