HV100 Series High Performance Current Vector Inverter
87
Running command channel
selection terminal 2
Running command channel
selection terminal 1
Running command channel
OFF
OFF
Determined by function code 00.06
OFF
ON
0: the operation panel runs the
command channel
ON
OFF
1: terminal running command channel
ON
ON
2: communication running command
channel
23: Inverter Forbidden acceleration/deceleration command
When the terminal is valid, the inverter will not be affected by external signals (except shutdown command), and
maintain the current frequency running.
24: Inverter run forbidden command
When the terminal is valid, the inverter in operation is free to shut down, while starting is prohibited in standby state.
Mainly used for occasions requiring safety linkage
25: Switch to keypad run command
When the terminal is valid, the running command is forcibly converted from the current channel to the panel control,
the terminal is disconnected, and return to the previous running command channel.
26: Switch to terminal run command
When the terminal is valid, the running command is forcibly converted from the current channel to the terminal control,
the terminal is disconnected, and return to the previous running command channel.
27: Switch to communicate run command
When the terminal is valid, the running command is forcibly converted from the current channel to communication control,
the terminal is disconnected, and return to the previous running command channel.
28: Auxiliary frequency is cleared
Only valid for digital auxiliary frequency (00.08 = 0, 1, 2). When this function terminal is valid, the auxiliary frequency
will be cleared quantitatively, and the set frequency will be completely determined by the main given frequency.
29: Frequency source A switch to K*
B
This terminal is valid. If 00.09 (frequency combination algorithm) selects 6, the given frequency channel will be forcibly
switched to frequency source B, and the given frequency channel will be restored to A after being invalid.
30: Frequency source A switch to
A+
K*
B
This terminal is valid. If 00.09 (frequency combination algorithm) selects 7, the given frequency channel will be forcibly
switched to frequency source (A+k * B), and the given frequency channel will be restored to A after being invalid.
31: Frequency source A switch to
A
-K*
B
This terminal is valid. If 00.09 (frequency combination algorithm) selects 8, the given frequency channel will be
forcibly switched to frequency source (A-k * B), and the given frequency channel will be restored to A after being invalid.
32
:
Reservation
33
:
PID control input
When the frequency given channel is PID given, and the PID input mode is manual input, the terminal is valid, and PID
running is entered. Please refer to F8 group parameter setting for detailed function codes.
34
:
PID control pause
Used to realize pause control of PID in running. When the terminal is valid, PID adjustment stops, and the frequency of
inverter stops running at the current frequency. After the terminal is invalid, PID adjustment will continue, and the operating
frequency will change with the change of adjustment amount.
35: Swing frequency control input
When the swing frequency starting mode is manual input, the swing frequency function is valid when the terminal is
valid. If it is invalid, it will run at the preset frequency of swing frequency. Please refer to the description of function code
09.55 ~ 09.65.
36: Swing frequency control pause
Terminal and COM short circuit, inverter pause the operation mode of swing frequency, and the frequency of inverter
stops running at the current frequency; After the terminal is invalid, continue to swing frequency running.
37: Swing frequency state reset
When this function is selected, whether in automatic or manual input mode, closing this terminal will clear the
frequency swing state information memorized in the inverter. After disconnecting this terminal, the swing frequency starts
again (if there is a preset frequency, run the preset frequency first). Please refer to the description of function code 09.55 ~
09.65.
38
:
PLC control input
When the PLC input mode is manually input through the defined multi-function terminal, the terminal is valid, and when
the operation command arrives, the PLC runs normally; If the terminal is invalid, when the running command arrives, it will
run at zero frequency.
39
:
PLC pause
It is used to realize pause control of the running PLC process. If the terminal is valid, the inverter runs at zero
frequency, and the PLC does not time; After the terminal is invalid, the inverter starts in the way of speed tracking, and
continues the PLC running. Please refer to the description of function code 09.00 ~ 09.53.