HV100 Series High Performance Current Vector Inverter
117
Figure 012-1 Schematic diagram of energy consumption braking
12.04
Power failure restart settings
0
~
2
0
0: Prohibited
When the power is turned on after power failure, the inverter will not run automatically.
1: Starting from starting frequency
When the power is turned on after power failure, if the starting conditions are met, the inverter will automatically start
running from the starting frequency point after waiting for the time defined in 12.05.
2: Speed tracking starting
When the power is turned on after a power failure, if the starting conditions are met, the inverter will automatically start and
run in speed tracking mode after waiting for the time defined in 12.05.
12.05
Waiting time for restart after power failure
0.0
~
60.0S
5.0
During the waiting time for restart, any operation command entered is invalid. If the shutdown command is input, the
inverter will automatically release the speed tracking restart state and return to the normal shutdown state.
Notes:
1: The valid restart after power failure is also related to the setting of 10.02. At this time, 10.02 must be set to 0.
2: This parameter will cause unexpected motor starting, which may cause potential damage to equipment and personnel.
Please use it with caution.
12.06
Automatic fault reset times
0
~
100
0
12.07
Automatic fault reset interval time
0.1
~
60.0S
3.0
100: Means unlimited times, that is, countless times
After a fault occurs during operation, the inverter stops outputting and displays the fault code. After the reset interval
set in 12.07, the inverter automatically resets the fault and restarts the operation according to the set starting mode.
The number of automatic fault resets is set by 12.06.When the number of fault reset is set to 0, there is no automatic reset
function and can only be reset manually. When 12.06 is set to 100, it means that the number of times is unlimited, that is,
countless times.
For IPM faults, external equipment faults, etc., the inverter is not allowed to conduct self-reset operation.
12.08
Cooling fan control
0
~
1
0
0: Automatic control mode
1: The power on process runs all the time
Time
Time
Braking backlash
Braking signal
Starting voltage
Bus voltage