HV100 Series High Performance Current Vector Inverter
22
Chapter VI Functions and Parameter Table
Symbols in the menu are described as follows
×
: Parameters that can be modified in any state
○
: Non modifiable parameters in operation state
◆
: Actual test parameter, cannot be modified
◇
: The manufacturer' parameters can only be modified by the manufacturer, but not by the user.
000 group-Basic Parameters
Function
code
Name
Content
Setting range
Factory
Alteration
00.00
LCD language
(only valid for LCD
keypad)
0: Chinese
1: English
0
~
1
0
○
00.01
Functional macro
definition
0: General model
1: Single pump constant pressure water supply mode
2: One inverter with two power (1 variable frequency
pump +2 power frequency pumps) water supply mode
3: Three-pump cycle soft start (3 variable frequency
pumps) water supply mode
4: Solar pump water supply mode
5: CNC machine tool control mode
6: Fire patrol mode
7: EPS power mode
8
~
20:Reserved
Note: Please initialize parameters before setting
macro functions.
0
~
20
0
×
00.02
Control Mode
0: Common V/F Control (manual torque boost)
1: Advanced V/F Control (Automatic torque boost)
2: SVC mode
(
SVC
)
3: Reserved
4: Separatable V/F Control
Note: this parameter cannot be initialized, please
modify it manually
0
~
4
Type
setting
×
00.03
Run command
channel selection
0: The keypad runs the command channel
1: Terminal operation command channel
2: Communication operation command channel
0
~
2
0
○