HV100 Series High Performance Current Vector Inverter
63
Figure 00-2 Schematic diagram of acceleration time and deceleration time
00.18
Running direction setting
0
~
2
0
0: Forward direction
When this mode is selected, the actual output phase sequence of the inverter is consistent with the default phase
sequence of the system. At this time, the keys
RUN
on the panel and FWD terminal functions become forward
control.
1: Reverse direction
When this mode is selected, the actual output phase sequence of the inverter will be opposite to the default phase
sequence of the system. At this time, the functions of keys
RUN
and FWD terminals on the panel are changed to
reverse control.
2. Forbidden reverse operation
In any case, the motor can only run forward. This function is suitable for situations where reverse operation may bring
danger or property loss. Given the reverse command, the inverter runs at zero speed.
Tips
:
This function code setting is valid for running direction control of all running command channels.
00.19
Carrier frequency setting
1.0
~
16.0KHz
Model setting
0.4
~
4.0KW
6.0KHz
1.0
~
16.0KHz
5.5
~
30KW
4.5KHz
1.0
~
16.0KHz
37
~
132KW
3.0KHz
1.0
~
10.0KHz
160
~
630KW
1.8KHz
1.0
~
5.0 KHz
This function code is used to set the carrier frequency of PWM wave output by inverter. The carrier frequency will affect
the noise when the motor is running, and the carrier frequency can be appropriately increased to meet the requirements
when silent operation is required. However, increasing the carrier frequency will increase the calorific value of the inverter
and the electromagnetic interference to the outside world.
When the carrier frequency exceeds the factory set value, the inverter needs to be derated. Generally, the inverter
current needs to be derated by about 5% for every 1KHz increase of download wave.
00.20
User password
0
~
65535
0
The user password setting function is used to prohibit unauthorized personnel from consulting and modifying function
parameters.
In order to avoid misoperation, user passwords less than 10 are invalid.
When setting the user password, enter any number not less than 10, press the key
E N T E R
to confirm, and the
password will take effect automatically after 3 minutes.
When you need to change the password, select the 00.20 function code, press the key
E N T E R
to enter the
password verification state, enter the modification state after the password verification is successful, enter a new password,
press the key
E N T E R
to confirm, and the password will automatically take effect after 3 minutes.
Please keep your password properly. If you forget it, please ask the manufacturer for service.
Tips
:
Please keep the password, and consult the manufacturer if it is lost.
Output frequency
Max output frequency
Time