HV100 Series High Performance Current Vector Inverter
69
Figure 01-7 Schematic diagram of forward and reverse dead time
01.35
Forward and reverse switching mode
0
~
1
0
0: Over 0Hz frequency switching
1: Over start frequency switching
01.36
Emergency stop standby deceleration time
0.1
~
3600.0S
1.0
For details, please refer to the function description of No. 10 in the digital input terminal (07.00
~
07.06).
01.37
Current holding time for DC braking during shutdown
0.0
~
100.0S
0.0
002 Group- Motor parameters
02.00
Selection of motor type
0
~
1
0
0: AC asynchronous motor
1: reserved
02.01
Motor rated Power
0.4
~
999.9KW
Model setting
02.02
Motor rated frequency
0.01Hz
~【
00.12
】
Max output frequency
50.00
02.03
Motor rated speed
0
~
60000RPM
Model setting
02.04
Motor rated voltage
0
~
999V
Model setting
02.05
Motor rated current
0.1~6553.5A
Model setting
Notes:
The above function codes must be set according to the motor nameplate parameters. Please configure the
corresponding motor according to the power of the inverter. If the power difference is too large, the control performance of
the inverter will obviously decrease.
02.06
Stator resistance of asynchronous motor
0.01
~
20.000Ω
Model setting
02.07
Rotor resistance of asynchronous motor
0.01
~
20.000Ω
Model setting
Time
Output
frequency